Current harmonic analysis for AC traction substation with power balancer

dc.contributor.authorBlahník, Vojtěch
dc.contributor.authorStraka, Miloš
dc.contributor.authorPittermann, Martin
dc.date.accessioned2022-02-07T11:00:13Z
dc.date.available2022-02-07T11:00:13Z
dc.date.issued2021
dc.description.abstract-translatedThis paper describes results of the harmonic analysis of currents harmonic analysis performed for an advanced AC traction Substation. AC traction substation feeding 25 kV / 50 Hz traction catenary and provide power symmetrization by semiconductor device called electronic balancer. The analysis is concern to currents of electronic balancer part of substation and the grid currents corresponding with quality of taken energy. The harmonic currents components are evaluate with the respect to the switching frequency of IGBTs (250 Hz), modulation technique (PS-PWM) and dead time duration (10 μs). The results are evaluated on the created model of the AC traction substation with multilevel converter topology, having the nominal power of 12.5 MVA.en
dc.format4 s.cs
dc.format.mimetypeapplication/pdf
dc.identifier.citationBLAHNÍK, V. STRAKA, M. PITTERMANN, M. Current harmonic analysis for AC traction substation with power balancer. In International Conference on Applied Electronics (AE 2021) : /proceedings/. Pilsen: University of West Bohemia, 2021. s. 17-20. ISBN: 978-80-261-0972-3 , ISSN: 1803-7232cs
dc.identifier.doi10.23919/AE51540.2021.9542908
dc.identifier.isbn978-80-261-0972-3
dc.identifier.issn1803-7232
dc.identifier.obd43933667
dc.identifier.uri2-s2.0-85116501679
dc.identifier.urihttp://hdl.handle.net/11025/46748
dc.language.isoenen
dc.project.IDEF18_069/0009855/Elektrotechnické technologie s vysokým podílem vestavěné inteligencecs
dc.project.IDSGS-2021-021/Výzkum a vývoj perspektivních technologií v elektrických pohonech a strojích IVcs
dc.publisherUniversity of West Bohemiaen
dc.relation.ispartofseriesInternational Conference on Applied Electronics (AE 2021) : /proceedings/en
dc.rights© University of West Bohemiaen
dc.rights.accessopenAccessen
dc.subject.translatedtraction substationen
dc.subject.translatedpower balanceren
dc.subject.translatedharmonic analysisen
dc.subject.translatedgrid current qualityen
dc.titleCurrent harmonic analysis for AC traction substation with power balanceren
dc.typekonferenční příspěvekcs
dc.typeConferenceObjecten
dc.type.statusPeer-revieweden
dc.type.versionpublishedVersionen