Four-leg transformer with defined zero sequence impedance for ground fault compensation

dc.contributor.authorRezaei, Mohsen
dc.contributor.authorTalla, Jakub
dc.contributor.authorKomrska, Tomáš
dc.contributor.authorPeroutka, Zdeněk
dc.date.accessioned2022-02-07T11:00:14Z
dc.date.available2022-02-07T11:00:14Z
dc.date.issued2021
dc.description.abstract-translatedSingle-phase ground faults are the most common faults in medium-voltage distribution grids. High-impedance grid grounding using a special four-leg transformer is discussed in the paper. The transformer’s zero-sequence impedance differs from positive-sequence impedance and it is designed to compensate the earth faults currents in Medium Voltage (MV) distribution grids when single-phase ground fault occurs. The designed transformer can replace the traditional arc suppression coils (ASC) in the case where no distribution transformer neutral is available or distributed compensation is required. Alternatively, the transformer can operate in parallel with the ASC.en
dc.format7 s.cs
dc.format.mimetypeapplication/pdf
dc.identifier.citationREZAEI, M. TALLA, J. KOMRSKA, T. PEROUTKA, Z. Four-leg transformer with defined zero sequence impedance for ground fault compensation. In International Conference on Applied Electronics (AE 2021) : /proceedings/. Pilsen: University of West Bohemia, 2021. s. 157-163. ISBN: 978-80-261-0972-3 , ISSN: 1803-7232cs
dc.identifier.doi10.23919/AE51540.2021.9542922
dc.identifier.isbn978-80-261-0972-3
dc.identifier.issn1803-7232
dc.identifier.obd43933696
dc.identifier.uri2-s2.0-85116419417
dc.identifier.urihttp://hdl.handle.net/11025/46753
dc.language.isoenen
dc.publisherUniversity of West Bohemiaen
dc.relation.ispartofseriesInternational Conference on Applied Electronics (AE 2021) : /proceedings/en
dc.rights© University of West Bohemiaen
dc.rights.accessopenAccessen
dc.subject.translatedsingle earth faulten
dc.subject.translateddistribution griden
dc.subject.translatedpetersen coilen
dc.subject.translatedzero sequence currenten
dc.subject.translatedtransformeren
dc.titleFour-leg transformer with defined zero sequence impedance for ground fault compensationen
dc.typekonferenční příspěvekcs
dc.typeConferenceObjecten
dc.type.statusPeer-revieweden
dc.type.versionpublishedVersionen

Files