Induction Motor Under Open Phase Condition
Date issued
2024
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE
Abstract
If there is a one-phase interruption anywhere in the distribution network, it results in an asymmetrical power supply of the load. If there are other substations and transformers between the fault and the load, the voltage drop of the affected phase may decrease. This is dangerous for protections because they may not immediately assess the condition correctly. The paper deals with the issue of asymmetrical power supply of induction motors and the effect on their properties, especially warming.
Description
Subject(s)
induction motor, open phase condition, warming, symmetrical components